Master Bilt MCR-33-101 User Manual Page 4

  • Download
  • Add to my manuals
  • Print
  • Page
    / 6
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 3
4
BASE “C”
BASE “D”
BASE “E”
COND.
UNIT
MODEL* H.P.
BTUH
@ -10°F
SUCTION
TEMP.**
UNIT CONNECTION
SIZES
DIMENSIONS
SEE
DRAWING...
(PP. 4-5)
RECEIVER
PUMP-
DOWN
CAP. @ 90%
SHIP
WT.
(LB/KG)
MCA** MOP** RLA** LRA**
LIQUID
SUCTION
MCR-33-102, 500 LB. CAPACITY, 1.5 HOUR PULL DOWN TIME
MDLZ0331C 6 32,417 5/8 1
3
/
8
M5 17 560/255 50 70 30.3 150
BCLZ0750C 7
1
/
2
37,322 7/8 1
3
/
8
D 53.4 730/332 55 80 31.5 161
BCLZ0750E 7
1
/
2
37,322 7/8 1
3
/
8
D 53.4 730/332 32 40 16.1 83
MCR-33-102, 500 LB. CAPACITY, LESS THAN 1 HOUR PULL DOWN TIME
BCLZ1500C 15 70,782 7/8 1
5
/
8
F 116.1 990/450 90 125 52.6 278
BCLZ1500E 15 70,782 7/8 1
5
/
8
F 116.1 990/450 51 70 26.3 139
MCR-33-102, 500 LB. CAPACITY, LESS THAN 1 HOUR PULL DOWN TIME – WATER-COOLED CONDENSING UNITS
SCLZ100WC 10 54,800 7/8 1
3
/
8
E 105.3 910/414 66 100 42 215
SCLZ100WE 10 54,800 7/8 1
3
/
8
E 105.3 910/414 34 50 18.6 106
*VOLTAGE KEY:
“B” sufx = 208-230 or 230 volt, 60 cycle, one phase
“C” sufx = 200-230 or 208-230 volt, 60 cycle, three phase
“E" sufx = 460 volt, 60 cycle, three phase
**Based on 90°F ambient
***Electrical ratings for condensing unit only. See National Electrical Code if units are combined on a single circuit.
REFRIGERATION SYSTEM TECHNICAL SPECIFICATIONS
Page view 3
1 2 3 4 5 6

Comments to this Manuals